Groutec

Mechanical splicing system for horizontal and vertical

precast elements

Groutec is designed to connect the precast elements
either horizontally or vertically by positioning the
rebar inside coupler.

Groutec can also be used to make a transition
between rebar of different sizes. Please refer to
our installation instructions for the list of possible
combinations.

Easily connect two precast elements with no
requirement for in situ wet concrete joint.

Groutec couplers are marked to trace raw materials
and production batch data.

Use either direction for Vertical Connections, the In horizontal applications and in vertical applications
Groutec sleeve installed in the bottom element, the with the Groutec sleeve installed in the top element,
grout can simply be poured by gravity directly into the the connection is achieved by injecting the grout
sleeve cavity. through the inlet pipe.

2525 Armitage Ave
Melrose Park, IL 60160
708-493-9569
www.surebuilt-usa.com

11/26

SureBuilt
Concrete Forms & Accessories

PDF PAGE 2
========================================================================

Product Options
Part No. Description

SBGSSF Groutec Spice System Full

Groutec F

“F”, for Fully grouted, allows the connection of two
rebars without the need of any threading procedure.

Installation Sequence

1. Preposition Groutec onto the 2. Install reinforcement. 3. Proceed with casting. Once
formwork using a positioner. ready, open the formwork. Remove
plugs and positioners.

4. Transport element to its final 5. Inject non-shrink grout. Seal 6. Bracing can be removed after
position over the dowel bars, the coupler with plugs when grout drying time
straighten and brace. overflows.

Image labels: Groutec F; Fully grouted
Step 5 image: Few seconds
Step 6 image: 3 days

PDF PAGE 3
========================================================================

Groutec F

“F”, for Fully grouted, allows the connection of two
rebars without the need of any threading procedure.

Bar Size A B C D E F
Part No. in in
US mm in mm in mm in mm in mm
(mm) (mm)
SBDGF16 #4,#5 12,16 2-1/2 64 1-1/4 32 12-3/16 310 2 51
SBDGF20 #6 18,19,20 2-11/16 68 1-7/16 36 13 330 2-3/16 55
SBDGF22 #7 22 2-7/8 73 1-5/8 41 14-15/16 380 2-3/8 60
SBDGF25 #8 24,25,26 3-1/16 78 1-3/4 44 14-15/16 380 1 1 2-9/16 65
SBDGF28 #9 28,29 3-1/4 83 1-7/8 48 8-5/8 460 (25) (25) 2-3/4 70
SBDGF32 #10 32 3-7/16 88 2 51 11 500 2-15/16 75
SBDGF36 #11 34,36 3-7/8 98 2-3/16 55 14-1/8 580 3-3/16 81
SBDGF40 #14 40,43 4-1/16 103 2-7/16 62 16-3/4 600 3-9/16 90

Transition Splicing
Rebar Size

Part No. #1 Construction Site #2 Precast Facility
US mm US mm
SBDGF16 #5 16 #4 12,
SBDGF20 #6 18,19,20 #4, #5, #6 12,16,18
#4, #5, #6 12,16,18
SBDGF22 #7 22
#6 19,20
#4, #5, #6 12,16,18
SBDGF25 #8 24,25,26 #6 19,20
#7 22
#6 19,20
SBDGF28 #9 28,29
#7, #8 22,24,25,26
#6 19,20
SBDGF32 #10 32 #7, #8 22,24,25,26
#9 28,29
#8 24,25,26
SBDGF36 #11 34,36 #9 28,29
#10 32
#10 32
SBDGF40 #14 40,43
#11 34,36

Image labels: Groutec F; Fully grouted

PDF PAGE 4
========================================================================

UES EVALUATION REPORT
Number: 312
Originally Issued: 03/28/2014
Revised: 03/11/2024
Valid Through: 03/31/2025

DEXTRA MANUFACTURING CO., LTD.
247 Sarasin Road, Lumpini, Pathumwan
Bangkok, Thailand
www.dextragroup.com

DEXTRA GROUTEC PRECAST SPLICING SYSTEM FOR STEEL REINFORCING BARS
CSI Section: 03 21 00 Reinforcing Steel

1.0 RECOGNITION

Dextra Groutec Precast Splicing System for steel reinforcing bars recognized in this report has been evaluated for use as a mechanical splice for deformed steel reinforcing bars in reinforced concrete construction. The structural properties and physical characteristics of the Dextra Groutec Precast Splicing System for steel reinforcing bars comply with the intent of the provisions of the following codes and regulations:

• 2021, 2018, 2015, 2012, and 2009 International Building Code® (IBC)
• 2021, 2018, 2015, 2012, and 2009 International Residential Code® (IRC)
• 2020 City of Los Angeles Building Code (LABC) – attached Supplement
• 2020 City of Los Angeles Residential Code (LARC) – attached Supplement
• 2019 California Building Code (CBC) – attached Supplement
• 2019 California Residential Code (CRC) – attached Supplement
• 2013 Abu Dhabi International Building Code (ADIBC) – attached Supplement

2.0 LIMITATIONS

Use of the DEXTRA Groutec Precast Splicing System recognized in this report is subject to the following limitations:

2.1 The splice system shall be identified and installed in accordance with the applicable code, the manufacturer’s instructions, and this report. In the event of a conflict between this report and the manufacturer’s instructions, the more restrictive shall govern.

2.2 Installation shall be limited to Exposure Category F1, as defined in Section 19.3.1 of ACI 318-19 and -14, and Section 4.2.1 of ACI 318-11 and -08, as applicable.

2.3 Special inspection shall be provided in accordance with Section 4.3 of this report.

2.4 The minimum concrete cover shall be in accordance with IBC Chapters 7 and 19, and Sections 7.6 and 7.7 of ACI 318, whichever is more restrictive and shall be measured from the outer surface of the splice connectors.

2.5 Splice locations shall comply with applicable IBC and ACI 318 requirements and be noted on plans approved by the building official.

2.6 Under the 2018, 2015, 2012, and 2009 IBC or IRC, installations in special moment frames and special structural walls shall comply with Section 18.2.7 of ACI 318-14, or Section 21.1.6 of ACI 318-11 and –08, as applicable.

2.7 Under the 2021 IBC or IRC, mechanical splice systems used in special moment frames (SMF), SMF constructed of precast concrete, special structural walls, intermediate structural wall connections, and other applicable structures are only allowed as permitted in Chapter 18 of ACI 318-19, and as described in Sections 2.8 to 2.11 of this report.

2.8 Under the 2021 IBC or IRC, only Type 2 mechanical splices of ASTM A706 Grade 60 reinforcement, or ASTM A615 Grade 60 reinforcement satisfying the requirements of ACI 318-19 Section 20.2.2.5(b), shall be permitted in regions where plastic hinging may occur, and located within a distance equal to twice the member depth from the column or beam face for special moment frames or from critical sections where yielding of the rebar occurs as a result of lateral displacements beyond the linear range of behavior in accordance with ACI 318-19 18.2.7.2. It is unknown if mechanical splices of other grades of steel reinforcement in special moment frames and special structural walls are capable of resisting stress levels expected in yielding regions in accordance with ACI 318-19 R18.2.7 and this use is beyond the scope of this report.

2.9 Under the 2021 IBC or IRC, the ability of the included mechanical splice systems, when used on Grade 80 reinforcement, to resist forces and provide yielding in the vicinity of the intermediate precast structural wall connections between precast wall panels, or between wall panels and the foundation, in the plastic region in accordance with ACI 318-19 R18.5, has not been determined, and this use is beyond the scope of this report.

2.10 Under the IBC or IRC, mechanical splice systems used in special moment frames constructed using precast concrete are expected to experience flexural yielding in connection regions in accordance with ACI 318-19 and -14 R18.9 (ACI 318-11 and -08 R21.8), and this use is beyond the scope of this report.

This product described in this Uniform Evaluation Service (UES) Report has been evaluated as an alternative material, design or method of construction in order to satisfy and comply with the intent of the provisions of the code, as noted in this report, and for at least equivalence to that prescribed in the code in quality, strength, effectiveness, fire resistance, durability and safety, as applicable, in accordance with IBC Section 104.11. This document shall only be reproduced in its entirety.

Copyright © 2024 by International Association of Plumbing and Mechanical Officials. All rights reserved. Printed in the United States. Ph: 1-877-4IESRPT • Fax: 909.472.4171
web: www.uniform-es.org • 4755 East Philadelphia Street, Ontario, California 91761-2816 – USA

UES — UNIFORM EVALUATION SERVICES
ANAB — ACCREDITED
Page 1 of 12

PDF PAGE 5
========================================================================

UES EVALUATION REPORT
Number: 312
Originally Issued: 03/28/2014
Revised: 03/11/2024
Valid Through: 03/31/2025

2.11 Under the 2021 IBC or IRC, mechanical splices of Grade 80 reinforcement shall not be used to transfer forces between the diaphragm and the vertical elements of the seismic-force-resisting system in accordance with ACI 318-19 18.12.7.4.

2.12 Under the 2021, 2018, and 2015 IBC or IRC, deformed steel reinforcing bars used with the DEXTRA Groutec Precast Splicing mechanical splice systems shall comply with ACI 318-19 and -14 Section 20.2.2.4 and Table 20.2.2.4(a) for the intended structural usage and application.

2.13 Under the 2021 IBC, for structures regulated by Chapter 18 of ACI 318-19 (as required by 2021 IBC Section 1905.1), to splice uncoated, deformed reinforcing bars resisting earthquake-induced flexure, axial force, or both, in special moment frames, special structural walls, and all components of special structural walls including coupling beams and wall piers, with the Dextra Groutec Precast Splicing System, mill certificates of reinforcing bars shall be submitted to the building official and the special inspector as evidence that the steel reinforcing bars comply with ACI 318-19 Section 20.2.2.5.

2.14 Under the 2018 IBC, for structures regulated by Chapter 18 of ACI 318-14 (as required by 2018 IBC Section 1905.1), to splice uncoated, deformed reinforcing bars resisting earthquake-induced flexure, axial force or both, in special moment frames, special structural walls, and all components of special structural walls including coupling beams and wall piers, with the Dextra Groutec Precast Splicing System, mill certificates of reinforcing bars shall be submitted to the building official and the special inspector as evidence that the steel reinforcing bars comply with ACI 318-14 Section 20.2.2.5.

2.15 Under the 2015 IBC, for structures regulated by Chapter 21 of ACI 318-14 (as required by 2015 IBC Section 1905.1), to splice uncoated, deformed reinforcing bars resisting earthquake-induced flexure, axial force, or both, in special moment frames, special structural walls, and all components of special structural walls including coupling beams and wall piers, with the Dextra Groutec Precast Splicing System, mill certificates of reinforcing bars shall be submitted to the building official and the special inspector as evidence that the steel reinforcing bars comply with ACI 318-14 Section 20.2.2.5.

2.16 Under the 2012 IBC, for structures regulated by Chapter 21 of ACI 318-11 (as required by 2012 IBC Section 1905.1), to splice uncoated, deformed reinforcing bars resisting earthquake-induced flexure, axial force, or both, in special moment frames, special structural walls, and all components of special structural walls including coupling beams and wall piers, with the Dextra Groutec Precast Splicing System, mill certificates of reinforcing bars shall be submitted to the building official and the special inspector as evidence that the steel reinforcing bars comply with ACI 318-11 Section 21.1.5.2.

2.17 Under the 2009 IBC, for structures regulated by Chapter 21 of ACI 318-08 (as required by 2009 IBC Section 1908.1), to splice uncoated, deformed reinforcing bars resisting earthquake-induced flexural and axial forces in frame members, structural walls and coupling beams, with the Dextra Groutec Precast Splicing System, mill certificates of reinforcing bars shall be submitted to the building official and the special inspector as evidence that the steel reinforcing bars comply with ACI 318-08 Section 21.1.5.2.

2.18 The Dextra Groutec Precast Splicing System shall be used with nonshrink grout complying with Section 4.2.2 of this report.

2.19 The use of the Dextra Groutec Precast Splicing System in fire-resistance-rated construction is outside the scope of this evaluation report.

2.20 The Dextra Groutec Precast splicing system for steel reinforcing bars recognized in this report is produced in Bangkok, Thailand.

3.0 PRODUCT USE

3.1 General: The Dextra Groutec Precast Splicing System is a mechanical splice for deformed steel reinforcing bars (rebars) installed in reinforced concrete structural members. The systems conform to Section 25.5.7.1 of ACI 318-19 and -14 for the 2021, 2018, and 2015 IBC, and Section 12.14.3.2 of ACI 318-11 for the 2012 IBC (Section 21.1.6 of ACI 318-08 for the 2009 IBC), for use as tension and compression mechanical splices of deformed steel reinforcing bars (rebars). The system also complies with Section 18.2.7.1 of ACI 318-19 and -14 for the 2018 and 2015 IBC, and Section 21.1.6.1 of ACI 318-11 for the 2012 IBC (ACI 318-08 for the 2009 IBC), as Type 1 and Type 2 mechanical splices. The Groutec Precast Splicing System may also be used where an engineering design is submitted in accordance with Section R301.1.3 of the IRC as illustrated in Tables 1 and 2 of this report and consists of:

Groutec L Mechanical splice
Groutec F Mechanical splice

3.2 Design and Installation

The Dextra Groutec Precast Splicing System shall be designed and installed in accordance with the IBC, ACI 318, this evaluation report, and the manufacturer’s published installation instructions. Where conflicts occur, the more restrictive shall govern. Installation shall be limited to Exposure Category F1, as defined in Section 19.3.1 of

Page 2 of 12

PDF PAGE 6
========================================================================

UES EVALUATION REPORT
Number: 312
Originally Issued: 03/28/2014
Revised: 03/11/2024
Valid Through: 03/31/2025

The IAPMO Uniform Evaluation Service Mark of Conformity may also be used as shown below:

UES
IAPMO UES ER-312

6.0 EVIDENCE SUBMITTED

6.1 Data submitted in accordance with the ICC-ES Acceptance Criteria for Mechanical Connector Systems for Steel Reinforcing Bars (AC133).

6.2 Test reports submitted are from laboratories in compliance with ISO/IEC 17025.

7.0 STATEMENT OF RECOGNITION

This evaluation report describes the results of research completed by IAPMO Uniform Evaluation Service on Dextra Groutec Precast Splicing System For Steel Reinforcing Bars to assess conformance to the codes shown in Section 1.0 of this report and serves as documentation of the product certification. Products are manufactured at locations noted in Section 2.20 of this report under a quality control program with periodic inspection under the supervision of IAPMO UES.

For additional information about this evaluation report please visit
www.uniform-es.org or email us at info@uniform-es.org

Page 5 of 12

PDF PAGE 7
========================================================================

UES EVALUATION REPORT
Number: 312
Originally Issued: 03/28/2014
Revised: 03/11/2024
Valid Through: 03/31/2025

TABLE 1—DIMENSIONS OF GROUTEC L COUPLERS¹

Bar mm | Bar No. | A mm | B mm | C mm | D mm | E mm | Minimum rebar engagement length² mm | Maximum rebar engagement length² mm
16 | #5 | 61 | 44 | 182 | 25 | 20 | 145 | 155
20 | #6 | 65 | 48 | 195 | 25 | 20 | 150 | 160
22 | #7 | 65 | 48 | 195 | 25 | 20 | 150 | 160
25 | #8 | 68 | 50 | 220 | 25 | 20 | 165 | 180
28 | #9 | 81 | 62 | 290 | 25 | 20 | 225 | 240
32 | #10 | 81 | 62 | 290 | 25 | 20 | 225 | 240
36 | #11 | 95 | 72 | 340 | 25 | 20 | 270 | 285
40 | – | 95 | 72 | 340 | 25 | 20 | 270 | 285

For inches: 1 mm = 0.04 inch
¹ Coupler dimensions in Table 1 of this report as shown in Figure 1 of this report are nominal dimensions.
² Embedment lengths are illustrated in Figure 1A of this report.

FIGURE 1—GROUTEC L COUPLERS SECTIONAL VIEW
Diagram labels: A, B, C, D, E

FIGURE 1A—GROUTEC L COUPLERS EMBEDMENT VIEW
Diagram labels: E min, E max, C

Page 6 of 12

PDF PAGE 8
========================================================================

UES EVALUATION REPORT
Number: 312
Originally Issued: 03/28/2014
Revised: 03/11/2024
Valid Through: 03/31/2025

FIGURE 2—GROUTEC L COUPLERS FITTED TO REINFORCING BARS

FIGURE 3—GROUTEC L COUPLERS APPLICATIONS IN REINFORCED CONCRETE

Page 7 of 12

PDF PAGE 9
========================================================================

UES EVALUATION REPORT
Number: 312
Originally Issued: 03/28/2014
Revised: 03/11/2024
Valid Through: 03/31/2025

TABLE 2—DIMENSIONS OF GROUTEC F COUPLERS¹

Bar mm | Bar No. | A mm | B mm | C mm | D mm | E mm | F mm | Construction site² Length Ec min mm | Construction site² Length Ec max mm | Factory site² Length Ec min mm | Factory site² Length Ec max mm
12 | #4 | 64 | 32 | 310 | 25 | 25 | 51 | 122 | 152 | 142 | 152
16 | #5 | 64 | 32 | 310 | 25 | 25 | 51 | 122 | 152 | 142 | 152
20 | #6 | 68 | 36 | 330 | 25 | 25 | 55 | 137 | 167 | 147 | 157
22 | #7 | 73 | 41 | 380 | 25 | 25 | 60 | 167 | 167 | 167 | 177
25 | #8 | 78 | 44 | 380 | 25 | 25 | 65 | 167 | 197 | 167 | 177
28 | #9 | 83 | 48 | 460 | 25 | 25 | 70 | 207 | 237 | 207 | 217
32 | #10 | 88 | 51 | 500 | 25 | 25 | 75 | 227 | 257 | 227 | 237
36 | #11 | 98 | 55 | 580 | 25 | 25 | 81 | 267 | 297 | 267 | 277
40 | #14 | 103 | 62 | 600 | 25 | 25 | 90 | 287 | 317 | 267 | 277

For inches: 1 mm = 0.04 inch
¹ Coupler dimensions in Table 2 of this report as shown in Figure 4 of this report are nominal dimensions.
² Embedment lengths are illustrated in Figure 5 of this report.

FIGURE 4—GROUTEC F COUPLERS SECTIONAL VIEW
Diagram labels: A, B, C, D, E, F

FIGURE 5—GROUTEC F COUPLERS EMBEDMENT VIEW
#1 Construction Site
#2 Precast Factory
Minimum embedment length
Maximum embedment length
Minimum embedment length
Maximum embedment length

Page 8 of 12

PDF PAGE 10
========================================================================

UES EVALUATION REPORT
Number: 312
Originally Issued: 03/28/2014
Revised: 03/11/2024
Valid Through: 03/31/2025

FIGURE 6—GROUTEC F COUPLERS FITTED TO REINFORCING BARS

FIGURE 7—GROUTEC F COUPLERS APPLICATIONS IN REINFORCED CONCRETE

Page 9 of 12

PDF PAGE 11
========================================================================

UES EVALUATION REPORT
Number: 312
Originally Issued: 03/28/2014
Revised: 03/11/2024
Valid Through: 03/31/2025

CITY OF LOS ANGELES SUPPLEMENT

DEXTRA MANUFACTURING CO., LTD.
247 Sarasin Road, Lumpini, Pathumwan
Bangkok, Thailand
www.dextragroup.com

DEXTRA MECHANICAL SPLICE SYSTEM
CSI Division: 03 00 00—CONCRETE
CSI Section: 03 21 00—Reinforcing Steel

1.0 RECOGNITION

The DEXTRA Groutec Precast Splicing System described in ER-312 and this supplemental report has been evaluated for use as mechanical splices for deformed steel reinforcing bars (rebar) in reinforced concrete structural members. The DEXTRA Groutec Precast Splicing System has been evaluated for structural performance properties, subject to the requirements in ER-312 and this supplemental report. The DEXTRA Mechanical Splice System was evaluated for compliance with the following codes and regulations:

• 2020 City of Los Angeles Building Code (LABC)
• 2020 City of Los Angeles Residential Code (LARC)

2.0 LIMITATIONS

Use of the DEXTRA Groutec Precast Splicing System recognized in this supplement is subject to the following limitations shown in ER-312:

2.1 Continuous special inspections of the DEXTRA Groutec Precast Splicing System during installation shall be provided by Registered Deputy Inspectors as required by Section 1705 of the LABC. The Registered Deputy Inspector shall verify the following: hardware and equipment; cleaning and condition of the bars in accordance with the specifications and the applicable code; and the installation procedures comply with the specifications and the manufacturer’s published installation instructions.

2.2 The fabricator of the steel couplers shall be required to maintain a detailed procedure for material control and suitable procedures and records attesting that the specified coupler has been furnished. The applicable splice designation (Type 1 or Type 2) or coating, as applicable, shall be included on each packaging assembly prior to shipment from the fabricator’s plant. The fabricator’s identification mark designation shall be established and on record prior to fabrication. Couplers that are not identifiable from marking and test records shall be tested to determine conformity to this report. The fabricator shall furnish an affidavit of compliance and test data shall be provided upon request.

2.3 The DEXTRA Groutec Precast Splicing System shall be selected at the job site by the Registered Deputy Inspector or by the building inspector and shall be tested by an approved testing agency in accordance with Section 1703 of the LABC. The test shall be conducted on each different rebar size and the frequency of tests shall be as follows: one out of the first ten splices; one out of the next ninety splices; one out of the next one hundred splices. The splice shall develop in tension or compression, as required, at least 125 percent of the specified yield strength of the bar in accordance with Section 25.5.7.1 of ACI 318-14. For Type 2 splices, the splice shall develop at least 100 percent of the specified tensile strength of the steel reinforcing bar.

For Type 2 splices only, if failure of the tested splice occurs prior to obtaining the 125-percent of the specified yield strength and the 100-percent of the specified tensile strength, then 25-percent of all couplers shall be tested for both specified yield strength and specified tensile strength. If failure of the tested Type 2 splice occurs with testing of the 25-percent requirement, as stated above, then all couplers shall be rejected.

2.4 Minimum concrete cover and spacing between bars or sleeves shall be provided in accordance with Section 1808.8.2 of the LABC.

2.5 The DEXTRA Groutec Precast Splicing System shall be installed in accordance with the applicable code, manufacturer’s installation instructions, and this supplement. A copy of the manufacturer’s installation instructions or specifications shall be available on-site for all Registered Deputy Inspectors.

2.6 Splice locations shall be noted on the plans approved by the building official.

2.7 Only qualified operators completely familiar with the installation procedures and specifications shall perform the splicing.

2.8 This supplement expires concurrently with ER-312.

3.0 CONCLUSIONS

The DEXTRA Groutec Precast Splicing System described in ER-312, complies with LABC and LARC, given the design and installation are in accordance with the 2018 International Building Code® (IBC) and 2019 California Building Code (CBC), or 2018 International Residential Code® (IRC) and 2019 California Residential Code (CRC). Additional requirements of the LABC Chapters 16, 17, 18 and 19 shall apply.

For additional information about this evaluation report please visit
www.uniform-es.org or email us at info@uniform-es.org

Page 10 of 12

PDF PAGE 12
========================================================================

UES EVALUATION REPORT
Number: 312
Originally Issued: 03/28/2014
Revised: 03/11/2024
Valid Through: 03/31/2025

CALIFORNIA SUPPLEMENT

DEXTRA MANUFACTURING CO., LTD.
247 Sarasin Road, Lumpini, Pathumwan
Bangkok, Thailand
www.dextragroup.com

DEXTRA MECHANICAL SPLICE SYSTEM
CSI Division: 03 00 00—CONCRETE
CSI Section: 03 21 00—Reinforcing Steel

1.0 RECOGNITION

The DEXTRA Groutec Precast Splicing System described in ER-312 and this CBC and CRC supplemental report has been evaluated for use as mechanical splices for deformed steel reinforcing bars (rebar) in reinforced concrete structural members. The DEXTRA Groutec Precast Splicing System has been evaluated for structural performance properties, subject to the requirements in ER-312 and this CBC and CRC supplemental report. The DEXTRA Groutec Precast Splicing System was evaluated for compliance with the following codes and regulations:

• 2019 California Building Code (CBC)
• 2019 California Residential Code (CRC)

2.0 LIMITATIONS

Use of the DEXTRA Groutec Precast Splicing System recognized in this supplement is subject to the following limitations in addition to the limitations shown in ER-312:

2.1 Calculations and specifications verifying compliance with the DEXTRA Groutec Precast Splicing System shall be submitted to the building official for approval at the time of permit application. The DEXTRA Groutec Precast Splicing System calculations shall be prepared by a Civil or Structural Engineer registered in the State of California.

2.2 Periodic special inspection shall be provided in accordance with Section 1705.3 or 1705A.3 (DSA and HCAi (formerly OSHPD)) of the CBC during installations of the DEXTRA Groutec Precast Splicing System.

2.3 Tests of reinforcing bars shall be provided in accordance with CBC Section 1909.2.4, 1910.2.2, or 1910A.2, as applicable.

2.4 The DEXTRA Groutec Precast Splicing System shall be installed in accordance with the CBC or CRC, as applicable, manufacturer’s installation instructions, and this supplement. A copy of the manufacturer’s installation instructions shall be available on-site for the building official and special inspector. Where conflicts occur, the more restrictive shall govern.

2.5 For work in accordance with CBC Chapter 19A (DSA and California Department of Health Care Access and Information (HCAi) (formerly OSHPD)), construction documents shall include the type and location of mechanical splices of reinforcement, as set forth in CBC Section 1901A.5.

2.6 For use in foundation walls, minimum concrete cover, and spacing between bars or sleeves shall be provided in accordance with Section 1808.8.2 or 1808A.8.2 of the CBC. Concrete cover and spacing shall be measured from the outer surface of the DEXTRA Groutec Precast Splicing System.

2.7 Type 2 mechanical splices shall be provided in accordance with CBC 1905A.1.10 for DSA and California Department of Health Care Access and Information (HCAi) (formerly OSHPD) regulated structures.

2.8 This supplement expires concurrently with ER-312.

3.0 CONCLUSIONS

The DEXTRA Groutec Precast Splicing System described in ER-312, complies with CBC and CRC, given the design and installation is in accordance with the 2018 International Building Code® (IBC) or 2018 International Residential Code® (IRC). Additional requirements of CBC Chapters 16, 17, 18, and 19 shall apply.

For additional information about this evaluation report please visit
www.uniform-es.org or email us at info@uniform-es.org

Page 11 of 12

PDF PAGE 13
========================================================================

UES EVALUATION REPORT
Number: 312
Originally Issued: 03/28/2014
Revised: 03/11/2024
Valid Through: 03/31/2025

ABU DHABI SUPPLEMENT

DEXTRA MANUFACTURING CO., LTD.
247 Sarasin Road, Lumpini, Pathumwan
Bangkok, Thailand
www.dextragroup.com

DEXTRA MECHANICAL SPLICE SYSTEM
CSI Division: 03 00 00—CONCRETE
CSI Section: 03 21 00—Reinforcing Steel

1.0 RECOGNITION

The DEXTRA Groutec Precast Splicing System described in ER-312 and this Abu Dhabi supplemental report has been evaluated for use as mechanical splices for deformed steel reinforcing bars (rebar) in reinforced concrete structural members. The DEXTRA Groutec Precast Splicing System has been evaluated for structural performance properties, subject to the requirements in ER-312 and this Abu Dhabi supplemental report. The DEXTRA Groutec Precast Splicing System were evaluated for compliance with the following codes and regulations:

• 2013 Abu Dhabi International Building Code (ADIBC)

2.0 LIMITATIONS

Use of the DEXTRA Groutec Precast Splicing System recognized in this supplement is subject to the following limitations in addition to the limitations shown in ER-312:

2.1 The DEXTRA Groutec Precast Splicing System described in ER-312, complies with Chapter 19 of the 2013 ADIBC, given the design and installation are in accordance with the 2009 International Building Code® (IBC).

2.2 The specified compressive strength of concrete, f′c shall not be less than 24 MPa (3,480 psi), when used in special moment frames and special structural walls in accordance with Section 21.1.4.2 of Appendix L in the 2013 ADIBC.

2.3 For structures regulated by Chapter 21 of ACI 318-08, as required by Section 21.1.5.2 of Appendix L in the 2013 ADIBC, where the DEXTRA Groutec Precast Splicing System is designed to resist earthquake-induced flexure and axial forces in frame members, structural walls, and coupling beams, mill certificates complying with ASTM A706M or BS EN4449 Class C, ASTM A615M Grades 280 and 420 or BS EN 4449 Class A or B reinforcement shall be submitted to the building official as evidence that the steel reinforcing bars are compliant.

2.4 Special inspection of the headed bars shall be provided at the jobsite as required by Sections 1704.4 and 1709.1 of the 2013 ADIBC. The special inspector is responsible for verifying identification of the deformed reinforcing bars, grade and size of reinforcing bars, proper joining of reinforcing bars with the precasted couplers as well as placement of the precasted coupler.

2.5 This supplement expires concurrently with ER-312.